MIL-STD-1623E(NAVY)
w/CHANGE 1
TABLE I. Material requirements - continued.
Category |
Material |
Specification |
Fire test |
Test limits |
|
Insulation continued |
Anti-sweat pipe insulation15/ |
EB Corp Spec 4013 |
Room/corner test (see applicable specification, Appendix A) |
Flame spread |
1 ft. on horizontal pipe runs MAX |
Ignition of target array |
None |
||||
Melting, dripping or flaming droplets |
None |
||||
Heat release rate (material only) |
11,384 Btu/minute (200 kW) MAX |
||||
Block insulation |
MIL-PRF- 2819 |
ASTM E84 |
Flame spread index |
0 MAX |
|
Smoke developed index |
0 MAX |
||||
Insulating felt |
MIL-I-16411 |
46 CFR 164.009 |
Pass8/ |
||
Insulating blanket |
21/ |
46 CFR 164.009 |
Pass8/ |
||
0n-deck insulation |
22/ |
46 CFR 164.009 |
Pass8/ |
||
Glass cloth |
MIL-C-20079 (All tests before and after treatment) |
||||
Type I, Classes 1, 3, 5, 7, 9 |
46 CFR 164.009 |
Pass8/ |
|||
Type I, Class 2 |
ASTM E84 |
Flame spread index |
20 MAX |
||
Smoke developed index |
10 MAX |
||||
Type I, Classes 4, 6, 8, 10 |
ASTM D6413 or FED-STD- 191 Method 5903.2 |
After flame and afterglow |
0 sec MAX |
||
Char length |
0 inch MAX |
||||
Flame travel |
1.5 inch MAX |
||||
Type II, Classes 1, 3, 4 |
46 CFR 164.009 |
Pass8/ |
|||
Type II, Class 2 |
ASTM E84 |
Flame spread index |
20 MAX |
||
Smoke developed index |
10 MAX |
||||
Cellular foam (Reefer spaces only) |
MIL-PRF- 24172 |
ASTM E84 (before and after humid aging) |
Flame spread index |
25 MAX |
|
Smoke developed index |
250 MAX |
||||
Foam thickness |
1.0 inch MAX |
||||
Melting, dripping, or flaming droplets |
None |
9